Benifits
- Level measurement in long straight pipes
- High temperature and pressure on Bypass tube, Level measurement
- Zero dead band, high penetration and accuracy
Specifications
| Radar Frequency | 76.2 to 80.2GHz dynamic FM sweep bandwidth 4GHz (On demand adjustment on the FM sweep bandwidth is available to comply with ISM requirements) |
| Measuring range | 10.0M / 40.0M |
| Dead Band | 0mm |
| Measuring principle | FMCW Radar TE01 Mode |
| Resolution | 0.1mm (10M for range) / 0.5mm (40M for range) |
| Accuracy | ±1mm (10m for range) / ±5mm (40m for range) |
| Antenna Material | PEEK material, Lensed Antenna |
| Antenna Beam | Modular lens RF beam 12° @ (Class 1 lens antenna) |
| Signal Output | 4-20mA, HART5(standard) / HART7 |
| Power Supply | 16V~36VDC / 2-wire |
| Process connection | DN50 Flange |
| Process temperature | ‐40 ~ 150℃/‐40 ~600℃ (Extra cooling fins are required ) |
| Ambient temperature | ‐40 ~ 85℃,≤95%RH |
| Process Pressure | ‐1 ~ 4MPa /‐4~32MPa(Extra reinforced flange members are required) |
| Local Configurable | PC desktop software(Radar PCManger) / 4 on panel push buttons/ Smartphone app and Wechat Mini-program (RadarMobileManger) / Vessel Side Meter |
| WIFI Connection | Bluetooth / LoRa / IOT |
| Comm.Protocol | HART / MODBUS / PROFIBUS (Optional) |
| Fail-safe | 22mA / 4mA/20.5mA (configurable) |
| Display | 160x80 dot matrix black and white monochrome display / with backlight(optional 128x64 dot matrix LCD / with backlight) |
| Enclosure material | Aluminium alloy made single chamber or dual chamber( 220VAC is available for dual chamber only) |
| Cable connector | M20x1.5 (⌀5...9mm) |
| IP rating | IP67 (electronic compartment filled with silica gel) |
| Approval | CNEX: Ex ia IIC T6 Ga |
| Package size | L x W x H 435mm x 275mm x 275mm |
| Application | Liquid, Powder, Paste |
Dimensions

Installing Applications